Overview of ..
This part of the Energy Efficiency Manual shows you how
to save energy in dual-duct variable air volume (VAV) air handling
systems, also called double duct systems. VAV dual-duct systems
have the potential of being efficient and comfortable, but they
often have significant opportunities for improvement.
In dual-duct systems, the air handling unit has two coils, a continuously
operating cooling coil and a continuously operating heating coil.
The cooling coil feeds chilled air into a cold air duct. The heating
coil feeds hot air into a hot air duct. The two ducts run in parallel
throughout the building. At each space, air is tapped from the two
ducts by a terminal unit. The terminal unit has a hot air damper
and a cold air damper. When the space thermostat calls for heating,
the hot air damper opens. When the thermostat calls for cooling,
the cold air damper opens.
Efficiency suffers if a terminal unit mixes chilled air with heated
under any conditions. The system may be designed to do this deliberately
under low conditioning loads to maintain a minimum air flow into
the spaces.
“Triple-duct” systems avoid air mixing. They are similar
in appearance to dual-duct systems. The main difference is a third
duct that carries unconditioned air (a mixture of return air and
outside air) for mixing with either the heated air or the chilled
air. If properly installed, triple-duct systems have no mixing losses,
except for leakage that occurs inside the terminal units.
Here are the energy conservation measures for optimizing efficiency
in VAV dual-duct systems. The largest opportunity for energy conservation
in VAV double duct systems is eliminating any mixing of heated air
and chilled air. Also, you can save fan energy by using accurate
fan modulation to follow the cooling or heating loads. Variable-speed
fans are the favored approach. VAV systems also allow you to use
energy saving thermostatic controls, including deadband thermostats
and temperature setback thermostats.
The dual-duct VAV system design is especially favorable for exploiting
the energy saving principle of the outside air economizer cycle.
Find the details here.

|